ENABLING LYNK II TO COMMUNICATE WITH NOARK DEVICES
When properly connected to a managed (closed-loop) network and set to use the NOARK protocol, LYNK II will transmit real-time parameters from the Discover Lithium battery, including voltage, current, temperature, state of charge, and fault conditions to a NOARK inverter-charger. LYNK II will also transmit charge voltage and current requests from the Discover Lithium battery to a NOARK inverter-charger.
LYNK ACCESS software for 64-bit Windows 10 / 11 is required to configure LYNK II settings for managed (closed-loop) CAN communication with NOARK inverter-chargers.
If there is a break in communication between the LYNK II and the inverter-charger for more than ten seconds, the inverter-charger will safely stop operation, so long as the BMS Lithium option is selected and the BMS_Err_Stop parameter is enabled on the NOARK inverter-charger. The inverter-charger will display an F58 BMS Communication Fault if communication is lost. The NOARK inverter-charger will check every five minutes and resume managed (closed-loop) operation if communication is re-established. However, if communication cannot be reestablished, the NOARK inverter-charger will need to be manually converted to a self-managed (open-loop) configuration to resume operation. Refer to the “NOARK Self-Managed (Open-Loop) Configuration” section.
NOTE |
---|
|