Skip to main content
Skip table of contents

Parallel Battery Installation Procedure (Parallel Wiring Kit)

The following instructions identify how to connect batteries and inverters in parallel using the HELIOS ESS Parallel Wire Kit (950-0068). One kit is required to parallel two batteries. Two kits are required to parallel three batteries.

caution.png

ELECTRIC SHOCK AND FIRE HAZARD

  • Take precautions to avoid bridging the terminals.

  • Do not contact the terminals with metal mountings, fixtures, or body parts.

Failure to follow these instructions may result in injury.

NOTICE

UNBALANCED BATTERY CELLS

Paralleling more than three batteries using the Parallel Wiring Kit may lead to unbalanced battery cells.

Failure to follow these instructions may result in equipment damage.

Install equipment following the standards set by the local authority having jurisdiction.

  1. Prepare the inverter and battery for wiring.

    1. If the inverter is wired to a power source, open the disconnect and set the inverter OFF.

    2. Use a DMM or other voltage measuring device to confirm the circuit is de-energized.

    3. If the circuit in which the battery is installed has a disconnect, open the disconnect to isolate the battery.

    4. Set both the battery BMS and the breaker to the OFF position.

    5. Use a DMM or other voltage measuring device to confirm the circuit is de-energized.

  2. Wire the inverter.

The Battery to Inverter Power Cables 2/0 AWG (950-0070) or 1/0 AWG (950-0071) are available to wire the batteries to the inverter. Select the cable set compatible with your inverter and inverter settings.

NOTE

  • When selecting the cables for use between the battery and the inverter-charger, note that a single pair of 2/0 AWG (950-0070) cables is suitable for current up to 200 A, and a single pair of 1/0 AWG (950-0071) cables is suitable for current up to 170 A.

  • The selection between using two pairs or a single pair of cables between the inverter and the batteries, is based on safely matching the load of the charger (A) and the cable's maximum current carrying capacity.

  1. Ensure the cable connections are clean and in working order.

    1. Connect the positive battery cable to a positive battery terminal on the inverter.

    2. Connect the negative battery cable to a negative terminal on the inverter.

When using ONE Set of Battery to Inverter cables

image-20250411-000415.png

Three Batteries in Parallel (Two Parallel Wire Kits 950-0068)

image-20250411-000649.png

Two Batteries in Parallel (One Parallel Wire Kit 950-0068)

  1. Connect the positive (+) battery cable in the HELIOS ESS Parallel Wire Kit (950-0068) to a receiving pin of the positive battery terminals on a battery at one end of the battery bank. Push the ends of cables against the receiving pins to secure the connection.

image-20250411-000834.png

Connect Cables to Battery Terminals

  1. Connect the negative (-) battery cable to a receiving pin of the negative battery terminals on the battery at the other end of the battery bank. Push the ends of cables against the receiving pins to secure the connection.

  2. Connect the positive (+) and negative (-) battery cables in the HELIOS ESS Parallel Wire Kit (950-0068) to the receiving pins of the positive and negative battery terminals on batteries as shown in the diagrams. Push the ends of cables against the receiving pins to secure the connection.

When Using TWO Sets of Battery to Inverter Cables

image-20250411-001250.png

Three Batteries in Parallel (Two Parallel Wire Kits 950-0068)

image-20250411-001353.png

Two Batteries in Parallel (One Parallel Wire Kit 950-0068)

  1. Connect one of the positive battery cables from the inverter to a battery on one end of the battery bank, and connect the other cable to the battery on the other end of the battery bank. Push the ends of cables against the receiving pins to secure the connection. Refer to the “Terminal Connections and Hardware” section.

image-20250411-000834.png

Connect Cables to Battery Terminals

  1. Connect one of the negative battery cables from the inverter to a battery on one end of the battery bank, and connect the other cable to the battery on the other end of the battery bank. Push the ends of cables against the receiving pins to secure the connection.

  2. Connect the positive (+) and negative (-) battery cables in the HELIOS ESS Parallel Wire Kit (950-0068) to the receiving pins of the positive and negative battery terminals on batteries as shown in the diagrams. Push the ends of cables against the receiving pins to secure the connection.


  1. Connect the CAN communication cables.

  2. Set all battery BMS to ON (ON/OFF key).

  3. Energize the system by setting all battery breakers to ON (close).

  4. Close the circuit disconnect if it is open.

NOTICE

TERMINAL BURNOUT

Failure to securely lock the ends of battery cables to the receiving pins on the battery will increase resistance and lower voltage, leading to burnout of the terminals and voiding of the warranty.

Failure to follow these instructions may result in equipment damage.

NOTE

  • Whenever replacing an old battery in a parallel string, use a battery of the same age, model, capacity, and voltage.

  • Before installing the battery in parallel, charge each battery to 100% SOC. Breakers, fuses, or other disconnects may open if the batteries are not at the same SOC.

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.