Monitoring Pack-Level Data 885-0142

Pack Statistics Addressing

Per the protocol:

Offset Address P = 1300 + 100 × n

  • n: Pack index (0 for Pack 1, up to 31 for Pack 32)

  • Each pack occupies 100 UINT16 registers.

 

Example Mapping

Pack

Start Address

1

1300

2

1400

3

1500

...

...

32

4300

 

Common Metrics per Pack (relative to P)

Metric

Offset

Notes

Total Pack Voltage

P+1

0.1 V

Total Pack Current

P+2

0.1 A, offset +3200

SOC

P+3

0.1 %

Charge/Discharge Cycles

P+25

Count

Cumulative Charge Energy

P+28

0.1 kWh, 2 words

Cumulative Discharge Energy

P+30

0.1 kWh, 2 words

Max Cell Voltage Diff

P+19

mV