Environmental Specifications

AES 210HV Environmental Specifications

Environmental Specifications

AES 210HV

Environmental Category

Outdoor (IP55 / NEMA 3R)

Rated Altitude

An altitude of up to 2,000 m (6,561 ft). Elevations greater do not significantly affect operating characteristics.

Charge Temperature

-30°C to 55°C (-22°F to 131°F)

Discharge Temperature

-30°C to 55°C (-22°F to 131°F)

Storage Temperature (a)(b)

-20°C to 45°C (- 4°F to 113°F)

Acoustic Noise at 1 m

≤75 dB

Relative Humidity

<95% (Non-condensing humidity)

(a) Storage outside of specified temperatures will result in permanent capacity loss and void the warranty.
(b) "Storage" refers to periods without Auxiliary AC Power with an active Thermal Management System.