Skip to main content
Skip table of contents

Thermal Management System (TMS) Specifications

AES 210HV Thermal Management System (TMS) Specifications

Specifications

AES 210HV

Product Name

8kW Energy Storage Chiller Unit

Product Model

BTMS-80-ES

Operating Ambient Temperature

-35 to +55°C (-31°F to +131°F)
(varies based on coolant and control logic)

Storage Temperature

-40 to +80°C (-40°F to +176°F)

Type of Coolant

50% water / 50% ethylene glycol

Refrigerant Type

R513A

Power Supply

200-275V AC 60Hz (208/240VAC Single Phase)

Refrigerating Capacity

≥8.0kW @ 18°C (64.4°F) outlet water & 45°C (113°F) ambient temperature

Heating Capacity (PTC Water Heater)

≥2.5kW @ 40°C (104°F) outlet water setting temperature

PTC Water Heater

PTC Ceramic Thermistor Semiconductor Resistor

Refrigeration COP

≥2.2 @ 45°C (113°F)

Power Factor

≥90%

Electric Power for Refrigeration(a)

≤4.5kW

Electric Power for Heating(b)

≤3.5kW

Pump Power Consumption

≤0.3kW

Standby Power

≤20W

Coolant Flow Rate

≥50 L/min @ 90kPa @ 18°C water
(≥ 13.2 Gallons/min @ 13.05 psi @ 64.4°F water)

Noise Level

≤75 dB

Total Weight

95±3kg

Work Altitude

<4000m

Corrosion Protection

Coating C4

(a) The average cooling power consumption between 25°C and 55°C (77°F and 131°F) is approximately 3,600 W.
(b) The average heating power consumption between -30°C and 5°C (-22°F and 41°F) is approximately 3,400 W. ​