Thermal Management System (TMS) Specifications
AES 210HV Thermal Management System (TMS) Specifications
Specifications | AES 210HV |
---|---|
Product Name | 8kW Energy Storage Chiller Unit |
Product Model | BTMS-80-ES |
Operating Ambient Temperature | -35 to +55°C (-31°F to +131°F) |
Storage Temperature | -40 to +80°C (-40°F to +176°F) |
Type of Coolant | 50% water / 50% ethylene glycol |
Refrigerant Type | R513A |
Power Supply | 200-275V AC 60Hz (208/240VAC Single Phase) |
Refrigerating Capacity | ≥8.0kW @ 18°C (64.4°F) outlet water & 45°C (113°F) ambient temperature |
Heating Capacity (PTC Water Heater) | ≥2.5kW @ 40°C (104°F) outlet water setting temperature |
PTC Water Heater | PTC Ceramic Thermistor Semiconductor Resistor |
Refrigeration COP | ≥2.2 @ 45°C (113°F) |
Power Factor | ≥90% |
Electric Power for Refrigeration(a) | ≤4.5kW |
Electric Power for Heating(b) | ≤3.5kW |
Pump Power Consumption | ≤0.3kW |
Standby Power | ≤20W |
Coolant Flow Rate | ≥50 L/min @ 90kPa @ 18°C water |
Noise Level | ≤75 dB |
Total Weight | 95±3kg |
Work Altitude | <4000m |
Corrosion Protection | Coating C4 |
(a) The average cooling power consumption between 25°C and 55°C (77°F and 131°F) is approximately 3,600 W. |