This manual provides general settings and is not a comprehensive guide to the programming and configuration of a specific installation. An installation may have unique conditions or use cases that require modification or adaptation of values. Installers must be capable of reviewing and adapting to the specifics of an installation and its specific use case, and optimizing settings where needed.

The key steps required to install and configure the LYNK II Communication Gateway with compatible Discover Lithium batteries and power conversion equipment are as follows:

  • Review and confirm equipment compatibility and correct sizing.

  • Configure the LYNK II CAN out pins to match the CAN in pins of the power conversion equipment.

  • Mount the LYNK II, connect the Discover battery communication network to the LYNK Port and then connect the LYNK II’s CAN Out Port to the power conversion equipment's communication network.

  • Terminate all networks correctly.

  • Using LYNK ACCESS software, set the LYNK II to the correct protocol to enable closed-loop communication between the Discover batteries and the power conversion equipment.

  • Set up the closed-loop configuration parameters on the power conversion equipment.

  • Set up user preferences and enable the use case using the power conversion control system.