These specifications are a general guide. Actual wire sizes and ratings should be verified based on use, load calculations, and local electrical codes.
|
Description |
Terminal ID |
Cable Type |
Notes |
|---|---|---|---|
|
Ground |
|
Bare or Insulated Copper |
Connect to a ground rod or Ufer ground-in pad for low-resistance grounding. |
|
Communication Cables |
LYNK II - RJ45 for Ethernet and CAN-based connections. |
Standard CAT6 or higher Ethernet Cable |
Run two separate cables: One dedicated for CAN bus communication with the inverter and another for the internet connection to the LYNK II Gateway. |
|
AC Auxiliary Connection |
J6 (Pre-Wired Connector) |
Use cable rated for wet and dry. |
Continuous current less than 20 A, circuit breaker 32 A, use #10 AWG copper minimum, as per NEC guidelines for ampacity. Adjust for longer runs or higher temperatures. |
|
P+/P- Terminations |
P+/P- |
A high-strand, flexible single-conductor cable insulated with XLPE, RHW-2, USE-2, PV Wire, or equivalent, is used for high-voltage DC applications. The cable should be rated above the expected maximum DC voltage in the specified configuration. |
Check the PCS or inverter manual for recommended or maximum wire size. |