Register Address |
Data Type |
Description |
Data Parsing |
Note |
|---|---|---|---|---|
|
P+1 |
UINT16 |
Enable insulation detection |
R/W |
1 – Enable insulation detection (valid for single cluster)
|
|
P+2 |
UINT16 |
Reset Reset Command |
R/W |
0 – No recovery
|
|
P+3 |
UINT16 |
Yellow light control |
R/W |
0 – Off
|
|
P+4 |
UINT16 |
PCS Fan Control |
R/W |
0 – Fan Off
|
|
P+5 |
UINT16 |
PACK Fire Alarm 1–16 |
R |
See Alarm Codes |
|
P+6 |
UINT16 |
PACK Fire Alarm 17–32 |
R |
See Alarm Codes |
|
P+7 |
UINT16 |
PACK MSD Alerts 1–16 |
R |
See Alarm Codes |
|
P+8 |
UINT16 |
PACK MSD Alerts 17–32 |
R |
See Alarm Codes |
Offset Address Formula:
P = 50501 + 50 × n (where n is the cluster number, 0 ≤ n < 32)