DATA ADDRESS TABLE
NOTE |
---|
|
Start Address | End Address | Data Storage Instructions | Reference |
---|---|---|---|
1 | 1000 | Provisionally reserved | — |
1001 | 1100 | Array (BAU) values and metrics, max 100 | |
1101 | 1200 | Array (BAU) status and other data, max 100 | |
1201 | 1300 | Reserved | — |
1301 | 4500 | Per Cluster metrics (BCU): 100 | |
4501 | 5000 | Battery cluster status | |
10001 | 30000 | BCU Cell voltage details, max 500 cells per cluster, 32 clusters (500 × 32 = 16000) | |
30001 | 38000 | Temperature details, max 250 temps per cluster, 32 clusters (250 × 32 = 8000) | |
38001 | 50000 | Reserved | — |
50001 | 50300 | Alarm parameters: 300 alarm fields | |
50301 | 50400 | System parameters: 100 reserved | |
50401 | 50410 | Time info: 10 reserved | |
50501 | 52100 | Cluster additional info: 50 fields × 32 clusters (50 × 32 = 1600) | |
52101 | 60000 | Reserved | — |
60101 | 60420 | Relay status: 10 fields × 32 clusters (10 × 32 = 320) | |
61001 | 61100 | Stack control data: 100 fields | |
62001 | 62006 | Liquid cooler operation status | |
62101 | 62105 | Liquid cooler temperature and pressure data |