The following supports Modbus Function Code 03 (Read Holding Registers), 06 (Write Single Holding Register), and 10 (Write Multiple Consecutive Holding Registers).
|
Register Address |
Data Type |
Description |
Data |
Note |
|---|---|---|---|---|
|
61001 |
UINT16 |
Enable High Voltage on Stack |
0 – N/A
|
EMS sends BMS the enable signal |
|
61002 |
UINT16 |
Turn off insulation detection |
0 – N/A
|
Other values are not applicable |
|
61003 |
UINT16 |
Open battery stack fault resumption |
0 – Disable fault reset
|
Other values are not applicable |
|
61004 |
UINT16 |
Reserved |
— |
Empty |
|
61005 |
UINT16 |
PCS Fan Control |
0 – N/A
|
— |
|
61006 |
UINT16 |
Cluster power-on enable 1–16 |
Bitwise enable for clusters 1–160 – Not enabled
|
Max 16 clusters (Bit mask: 16 bits) |
|
61007 |
UINT16 |
Cluster power-on enable 17–32 |
Bitwise enable for clusters 17–320 – Not enabled
|
Max 16 clusters (Bit mask: 16 bits) |