Skip to main content
Skip table of contents

Battery Stack Control

The following supports Modbus Function Code 03 (Read Holding Registers), 06 (Write Single Holding Register), and 10 (Write Multiple Consecutive Holding Registers).

Register Address

Data Type

Description

Data

Note

61001

UINT16

Enable High Voltage on Stack

0 – N/A
1 – Enable power on
2 – All cluster disconnect relays, power off

EMS sends BMS the enable signal

61002

UINT16

Turn off insulation detection

0 – N/A
1 – Turn off insulation detection
2 – Turn on but skip post-on check
3 – Turn on + polling

Other values are not applicable

61003

UINT16

Open battery stack fault resumption

0 – Disable fault reset
1 – Enable fault reset

Other values are not applicable

61004

UINT16

Reserved

Empty

61005

UINT16

PCS Fan Control

0 – N/A
1 – N/A

61006

UINT16

Cluster power-on enable 1–16

Bitwise enable for clusters 1–160 – Not enabled
1 – Enabled
Bit 0 – Cluster 1
Bit 1 – Cluster 2...

Max 16 clusters (Bit mask: 16 bits)

61007

UINT16

Cluster power-on enable 17–32

Bitwise enable for clusters 17–320 – Not enabled
1 – Enabled
Bit 0 – Cluster 17
Bit 1 – Cluster 18...

Max 16 clusters (Bit mask: 16 bits)