Battery Stack Control
The following supports Modbus Function Code 03 (Read Holding Registers), 06 (Write Single Holding Register), and 10 (Write Multiple Consecutive Holding Registers).
Register Address | Data Type | Description | Data | Note |
---|---|---|---|---|
61001 | UINT16 | Enable High Voltage on Stack | 0 – N/A | EMS sends BMS the enable signal |
61002 | UINT16 | Turn off insulation detection | 0 – N/A | Other values are not applicable |
61003 | UINT16 | Open battery stack fault resumption | 0 – Disable fault reset | Other values are not applicable |
61004 | UINT16 | Reserved | — | Empty |
61005 | UINT16 | PCS Fan Control | 0 – N/A | — |
61006 | UINT16 | Cluster power-on enable 1–16 | Bitwise enable for clusters 1–160 – Not enabled | Max 16 clusters (Bit mask: 16 bits) |
61007 | UINT16 | Cluster power-on enable 17–32 | Bitwise enable for clusters 17–320 – Not enabled | Max 16 clusters (Bit mask: 16 bits) |