Skip to main content
Skip table of contents

Full Cluster Status (SBCU)

Register Address

Data Type

Description

Unit / Notes

4501

UINT16

Cluster Total Voltage

0.1 V

4502

UINT16

Cluster Current

0.1 A, offset +3200

4503

UINT16

Cluster SOC

0.1 %

4504

UINT16

Cluster SOH

0.1 %

4505

UINT16

Cluster Ready Flag

1 = Ready, 0 = Not Ready

4506

UINT16

Cluster Isolation Switch Status

1 = Connected, 0 = Disconnected

4507

UINT16

Max Cell Voltage

mV

4508

UINT16

Min Cell Voltage

mV

4509

UINT16

Max Cell Temp

°C (actual value + 40°C)

4510

UINT16

Min Cell Temp

°C (actual value + 40°C)

4511

UINT16

Max Voltage Difference

mV

4512

UINT16

Max Temp Difference

°C

4513

UINT16

Cluster Communication Status

1 = Normal, 0 = Fault

4514

UINT16

Cluster Hardware Status

Bitmask

4515

UINT16

Cluster Software Status

Bitmask

4516

UINT16

Cluster Alarm Level 1 Flag

Bitmask (cell/voltage/temp alarms)

4517

UINT16

Cluster Alarm Level 2 Flag

Bitmask

4518

UINT16

Cluster Alarm Level 3 Flag

Bitmask

4519

UINT16

Cluster Maintenance Alarm Flag

Bitmask

4520

UINT16

Cluster Auxiliary Alarm Flag 1

Bitmask

4521

UINT16

Cluster Auxiliary Alarm Flag 2

Bitmask

4522

UINT16

Cluster Operation Status

1 = Running, 0 = Stopped

4523

UINT16

Cluster Fault Code

Code value (refer to fault table)

4524

UINT16

Number of SBMUs in Cluster

Integer count

4525

UINT16

Number of Temperature Sensors in Cluster

Integer count

4526

UINT16

Cluster Max Charging Current Limit

0.1 A

4527

UINT16

Cluster Max Discharging Current Limit

0.1 A

4528

UINT16

Cluster Charge/Discharge Cycle Count

Total cycles

4529

UINT16

Cluster Today's Charge Energy

0.1 kWh

4530

UINT16

Cluster Today's Discharge Energy

0.1 kWh

4531

UINT16

Available Charging Capacity

0.1 kWh

4532

UINT16

Available Discharging Capacity

0.1 kWh

4533–4534

UINT32

Cluster Accumulated Charging Energy

0.1 kWh

4535–4536

UINT32

Cluster Accumulated Discharging Energy

0.1 kWh

JavaScript errors detected