COMMUNICATION AND NETWORK DETAILS
NOTE |
|---|
For background information on the communication protocol, refer to GB/Z 19582.1-2004 Specification for Industrial Automation Networks Based on Modbus Protocol Part III. |
Ethernet (Modbus TCP/IP)
Default SBAU IP: 192.168.0.101
Default Port: 2404
Recommended EMS IP: 192.168.1.10
Protocol: Modbus TCP/IP (big-endian format)
Function Codes
0x03: Read Holding Registers
0x06: Write Single Register
0x10: Write Multiple Registers
All register addresses are in decimal and use UINT16 data types unless otherwise noted.