885-0126 AES CAB BAU Overview and EMS/MGC Integration Guide

Integration Guidelines

Ensure PCS power current = 0 before writing 61001 = 2 to shut down; BMS will forcibly open relays if current remains >0 for 5 seconds.

  • Use polling to scan 32 clusters using the offset address formula.

  • Ensure IP and MAC uniqueness for each SBAU on the EMS network.

  • SBAU firmware and configuration are managed via the official BMS software, which includes:

    • Relay test control

    • SOC/QMAX setup

    • Firmware upgrade via CAN