The following supports Modbus Function Code 03 (Read Holding Registers) only.

Register Address

Data Type

Data Content

Data

Unit

62101

UINT16

TMS Water Temperature

Resolution: 1°C/bit
Offset: -40°C
Range: -40~210°C

°C

62102

UINT16

TMS Return Temperature

Resolution: 1°C/bit
Offset: -40°C
Range: -40~210°C

°C

62103

UINT16

TMS Ambient Temperature

Resolution: 1°C/bit
Offset: -40°C
Range: -40~210°C

°C

62104

UINT16

TMS Inlet Pressure Value

Resolution: 0.1 bar/bit
Offset: 0
Range: 0–25.0 bar

bar

62105

UINT16

TMS Outlet Pressure Value

Resolution: 0.1 bar/bit
Offset: 0
Range: 0–25.0 bar

bar

62106

UINT16

Reserved

62107

UINT16

Reserved

62108

UINT16

Reserved

62109

UINT16

Reserved

62110

UINT16

Reserved

62111

UINT16

Reserved

62112

UINT32

Reserved

62114

UINT32

Reserved

Note: Validity of the data depends on the project's specific configuration.