Skip to main content
Skip table of contents

System Operating Parameters

Register Address

Data Type

Description

Data Unit

Note

50301

UINT16

Starting passive equalization starting voltage difference value

mV

50 mV

50302

UINT16

Minimum cell voltage value to initiate passive equalization

mV

3330 mV

50303

UINT16

Fan On Temperature

°C, +40°C

Real data +40°C

50304

UINT16

Fan Off Temperature

°C, +40°C

Real data +40°C

50305

UINT16

Fan Unit Voltage

mV

50306

UINT16

Max allowable current for single cluster charging

0.1 A

1400

50307

UINT16

Min allowable current for single cluster charging

0.1 A

300

50308

UINT16

Charging current reduction unit voltage value

mV

3450

50309

UINT16

Charge stop single voltage value

mV

3500

50310

UINT16

Max allowable current for single cluster discharging

0.1 A

1400

50311

UINT16

Min allowable current for single cluster discharging

0.1 A

300

50312

UINT16

Charging current reduction unit voltage value

mV

2950

50313

UINT16

Stop discharge cell voltage value

mV

2900

50314

UINT16

Pre-charge voltage

0.1 V

150

50315

UINT16

Cluster accumulation of total voltage differential alarm values

0.1 V

30

50316

UINT16

Cooling start-up temperature

°C, +40°C

70

50317

UINT16

Cooling stop temperature

°C, +40°C

68

50318

UINT16

Heating start-up temperature

°C, +40°C

50

50319

UINT16

Heating stop temperature

°C, +40°C

45

50320

UINT16

Self-circulating start-up temperature difference

°C, +40°C

5

50321

UINT16

Target temperature

°C, +40°C

63 / 70

50322

UINT16

Start passive equalization and stop voltage difference value

mV

30 mV