Register Address |
Data Type |
Description |
Data Unit |
Note |
|---|---|---|---|---|
|
50301 |
UINT16 |
Starting passive equalization starting voltage difference value |
mV |
50 mV |
|
50302 |
UINT16 |
Minimum cell voltage value to initiate passive equalization |
mV |
3330 mV |
|
50303 |
UINT16 |
Fan On Temperature |
°C, +40°C |
Real data +40°C |
|
50304 |
UINT16 |
Fan Off Temperature |
°C, +40°C |
Real data +40°C |
|
50305 |
UINT16 |
Fan Unit Voltage |
mV |
|
|
50306 |
UINT16 |
Max allowable current for single cluster charging |
0.1 A |
1400 |
|
50307 |
UINT16 |
Min allowable current for single cluster charging |
0.1 A |
300 |
|
50308 |
UINT16 |
Charging current reduction unit voltage value |
mV |
3450 |
|
50309 |
UINT16 |
Charge stop single voltage value |
mV |
3500 |
|
50310 |
UINT16 |
Max allowable current for single cluster discharging |
0.1 A |
1400 |
|
50311 |
UINT16 |
Min allowable current for single cluster discharging |
0.1 A |
300 |
|
50312 |
UINT16 |
Charging current reduction unit voltage value |
mV |
2950 |
|
50313 |
UINT16 |
Stop discharge cell voltage value |
mV |
2900 |
|
50314 |
UINT16 |
Pre-charge voltage |
0.1 V |
150 |
|
50315 |
UINT16 |
Cluster accumulation of total voltage differential alarm values |
0.1 V |
30 |
|
50316 |
UINT16 |
Cooling start-up temperature |
°C, +40°C |
70 |
|
50317 |
UINT16 |
Cooling stop temperature |
°C, +40°C |
68 |
|
50318 |
UINT16 |
Heating start-up temperature |
°C, +40°C |
50 |
|
50319 |
UINT16 |
Heating stop temperature |
°C, +40°C |
45 |
|
50320 |
UINT16 |
Self-circulating start-up temperature difference |
°C, +40°C |
5 |
|
50321 |
UINT16 |
Target temperature |
°C, +40°C |
63 / 70 |
|
50322 |
UINT16 |
Start passive equalization and stop voltage difference value |
mV |
30 mV |