Full Battery Array Status (SBAU)
The following supports Modbus Function Code 03 (Read Holding Registers) only.
Register Address | Data Type | Description | Unit / Notes |
---|---|---|---|
1101 | UINT16 | Operation Status of Battery Stack | Bit 0: Initialization status |
1102 | UINT16 | Cluster Operation Flag | Each bit identifies whether a cluster is in operation. |
1103 | UINT16 | Cluster Connection Status | 0 - no fault, 1 - fault |
1104 | UINT16 | Stack Ready Flag | 0 - not full, 1 - full |
1105 | UINT16 | Level 1 Alarm Flag | Bit bitmask: 1–32 for L1 alarms. |
1106 | UINT16 | Level 2 Alarm Flag | Bit bitmask: 1–32 for L2 alarms. |
1107 | UINT16 | Level 3 Alarm Flag | Bit bitmask: 1–32 for L3 alarms. |
1108 | UINT16 | Communication Alarm Flag | Bit bitmask: 1–32 for communication status. See Alarm Codes |
1109 | UINT16 | Hardware Fault Flag | Bit bitmask: 1–32 for hardware fault. See Alarm Codes |
1110 | UINT16 | Software Fault Flag | Bit bitmask: 1–32 for software fault. See Alarm Codes |
1111 | UINT16 | Maintenance Fault Flag | Bit bitmask: 1–32 for maintenance issue. See Alarm Codes |
1112 | UINT16 | Reserved | — |
1113 | UINT16 | Auxiliary Alarm Flag 1 | Bit bitmask See Alarm Codes |
1114 | UINT16 | Auxiliary Alarm Flag 2 | Bit bitmask See Alarm Codes |
1115 | UINT16 | Stack Operation Flag | Bit bitmask for cluster power-on state. |
1116 | UINT16 | Stack Isolation Switch Status | 0 - Off, 1 - On |
1117 | UINT16 | BMS Communication Status | Bitmask (e.g., EMS, PCS, Cluster, etc.) |
1118 | UINT16 | Battery System Time (Seconds) | Seconds since system startup |
1119 | UINT16 | System Self-check Status | 0 - Not passed, 1 - Passed |
1120 | UINT16 | Relay Closing Command Status | 0 - None, 1 - Executing, 2 - Successful, 3 - Failed |
1121 | UINT16 | Relay Opening Command Status | 0 - None, 1 - Executing, 2 - Successful, 3 - Failed |
1122 | UINT16 | Main Positive Relay Status | 0 - Open, 1 - Closed |
1123 | UINT16 | Main Negative Relay Status | 0 - Open, 1 - Closed |
1124 | UINT16 | Precharge Relay Status | 0 - Open, 1 - Closed |
1125 | UINT16 | Fault Count | Total fault occurrences |
1126 | UINT16 | First Fault Code | — |
1127 | UINT16 | First Fault Cluster No. | — |
1128 | UINT16 | First Fault Type | — |
1129 | UINT16 | System Operation Time | Seconds |
1130 | UINT16 | System Version Code | Software version ID |
1131 | UINT16 | Current Mode of Operation | 0 - Standby, 1 - Charging, 2 - Discharging |
1132 | UINT16 | System Time (Year) | e.g., 2025 |
1133 | UINT16 | System Time (Month) | 1–12 |
1134 | UINT16 | System Time (Day) | 1–31 |
1135 | UINT16 | System Time (Hour) | 0–23 |
1136 | UINT16 | System Time (Minute) | 0–59 |
1137 | UINT16 | System Time (Second) | 0–59 |