Skip to main content
Skip table of contents

Two Sol-Ark 3-Phase Inverters, One AES Cabinet

warning.png

ELECTRIC SHOCK AND FIRE HAZARD
Follow NEC guidelines for conductor size, insulation rating (≥1000 Vdc), and torque specs for safe and code-compliant installation.

Failure to follow these instructions may result in death or serious injury.

image-20251219-182245.png

Two Sol-Ark Inverters, One AES Battery Cabinet

When the AES Cabinet is paired with two Sol-Ark inverters, the AES Cabinet may limit the inverters to a maximum continuous output of 52/104 kW. Actual discharge performance depends on the inverter model’s battery-side power capacity, as shown below.

Full Load Duration (Operation at Max Power)

Inverter Model

Inverter Battery Discharge Limit

CAB-106

CAB-160

CAB-210

AC Output / Usable Storage / Estimated Runtime

30K-3P-208V

30 kW × 2 = 60 kW

52 kW* / 104 kWh / 2 hours

N/A

N/A

60K-3P-480V

60 kW × 2 = 120 kW

52 kW* / 104 kWh / 2 hours

78 kW* / 157 kWh / 2 hours

104 kW* / 209 kWh / 2 hours

* Curtailed by the battery.

These run time estimates assume continuous full-power discharge and operation within safe continuous discharge parameters. Final performance should match the site's energy demand and load profile.

System Scalability - Two Inverters, One AES Cabinet

image-20251127-212211.png

Ten Paralleled Inverters

Two Sol-Ark 30K/60K-3P inverters are paired with each AES battery cabinet.

In this setup:

  • 104 to 209 kWh of usable backup energy between two inverters

  • Discharge power is limited by the total inverter capacity or battery power limitation (max 52 to 120 kW)

  • On the backup side, up to ten inverters can be connected in parallel, providing 300-600 kW of continuous backup power and approximately 520-1,045 kWh of total backup energy (5 × 104 kWh / 5 × 209 kWh).

Grid-Tied (Non-Backup) Scalability

The number of inverters or batteries is unlimited for non-backup use. Each inverter runs independently, allowing systems to scale as large as needed for energy shifting, peak shaving, or other grid-interactive applications.

DC Battery Wiring – Two Inverters, One AES Cabinet

image-20250522-235755.png

Inverter to Cabinet DC Wiring

Each Sol-Ark 3P inverter has two battery input terminals, each rated at 50 A. The AES Cabinet connects to the inverter using:

  • Two positive and two negative #4 AWG conductors to each inverter.

  • Each conductor is protected by a 70 A fuse in the AES Cabinet’s built-in DC distribution box.

This setup ensures balanced current flow to each inverter’s internal DC/DC converter and supports 30-60 kW continuous charge/discharge, depending on the inverter model.

Communication – Two Inverters, One AES Cabinet

image-20251127-212804.png

Inverter - LYNK II - Cabinet Communication

In a two-to-one configuration, a LYNK II Gateway is required for each inverter to enable real-time, managed (closed-loop) control. The AES Cabinet communicates with one Sol-Ark inverter through one LYNK II Gateway (may be included with the battery cabinet), and with a second Sol-Ark inverter through a second LYNK II Gateway.

Wiring

  • Connect one cable from LYNK II #1 CAN port to the Sol-Ark inverter #1’s BMS port. Connect a second cable from LYNK II #1’s LYNK port to the J3 port on the AES Cabinet’s High Voltage Box. On most AES Cabinets, a CAT6 cable is already connected to the J3 port on the AES Cabinet’s High Voltage Box and is accessible from the LYNK II.

  • Connect a third cable from LYNK II #2 CAN port to the Sol-Ark inverter #2’s BMS port. Connect a fourth cable from LYNK II #2’s LYNK port to the J4 port on the AES Cabinet’s High Voltage Box.

NOTE

You can use a splitter/combiner, as shown below, to connect two LYNK II Gateways to the J3/J4 ports on the AES Cabinet through a single cable.

image-20260204-170828.png

Configure LYNK II

  1. Start LYNK ACCESS 2.5.0 or later and update both LYNK II Gateways to firmware to 2.5.0 or later.

  2. Connect to the first LYNK II device. From the LYNK ACCESS software’s LYNK tab, open the Cabinet Settings tile, enable Multi-LYNK, and set it as Primary.

image-20251209-222004.png
  1. Connect to the second LYNK II device, enable Multi-LYNK and set it as Secondary.

To confirm the system is working correctly, check the battery charging current values on the inverter. If values are 50% of the max, then the 2:1 Multi LYNK configuration is successful.

NOTE

  • Configure the LYNK II Gateways as specified.

  • In a two inverter/one AES Cabinet system:

    • If Multi LYNK is disabled in both LYNK II Gateways, only one of the connected LYNKs passes the AES Cabinet battery information to its inverter.

    • If Multi LYNK is disabled in one of the LYNK II Gateways and the other is enabled as Secondary, both LYNK II Gateways will pass AES Cabinet battery information to their respective inverters, potentially causing the charge or discharge current to exceed the maximum allowed (overcurrent) for the battery cabinet.

    • If Multi LYNK is enabled and both LYNK II Gateways are set as Primary, or both are set as Secondary, only one of them passes AES Cabinet battery information to the inverter. The charge/discharge current will be reduced by 50%.

The LYNK II communication link enables the inverter to receive real-time battery data, including state of charge, voltage, current, temperature, and charge/discharge limits, ensuring safe, accurate, and optimized operation.

This setup enables two inverters to manage and monitor the battery cabinet, receiving real-time data for state of charge, voltage, current, temperature, and charge/discharge limits from each LYNK II Gateway. Two independent LYNK II Gateways ensure precise, safe, and optimized performance with dual inverters.

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.