Skip to main content
Skip table of contents

Sol-Ark Inverter Configuration (Open Loop)

If closed-loop communication cannot be established and you need to resume operation, you may have to convert the Sol-Ark inverter to an open-loop configuration manually. Refer to the latest Discover Energy Systems documentation for battery values and the latest Sol-Ark documentation for menu navigation and details on the setup procedure.

NOTE

  • It is recommended that the Sol-Ark inverter be programmed with the appropriate open-loop settings before enabling closed-loop communication.

  • Depending on your system and particular use case, there may be other settings that require configuration. Refer to the inverter manual for information on these settings.

  1. Set the Discover Lithium batteries to ON and set the inverter-charger to ON.

  2. Using the touch screen and keypad on the inverter, navigate to System Setup > Battery Setup.

  3. Specify the battery settings according to the instructions in the tables that follow. Touch the Up and Down arrows to scroll through screens.

  4. Touch the check mark button to save changes.

  5. Exit and restart the inverter-charger.

Open Loop: System Setup > Battery Setup > Batt

Open Loop  Batt.png

Battery Setting - Sol-Ark Open-Loop Charge Settings

Batt Setup > Batt

Batt Capacity

Set to the number of Discover Lithium batteries x Ah capacity of each. For example, set to 628 Ah for two HELIOS ESS 52-48-16000 batteries, each rated 314 Ah capacity.

Max A Charge

For a single inverter, set to the lesser of the inverter’s maximum charge rate or the quantity of attached batteries multiplied by the battery’s maximum charge rating.

For example:

Single phase system with 12K-2P-N inverter and two HELIOS ESS 52-48-16000 batteries

  • Set the 12K-2P-N inverter to the lessor of the inverter’s maximum charge rate of 185 A, or 380 A for two HELIOS ESS 52-48-16000 batteries. (1)
    NOTE: Each HELIOS ESS battery is rated at a 200 A charge rate, but when connected in parallel, the maximum current is limited by internal busbars. For the recommended maximum current for paralleled HELIOS ESS, refer to the table in the Minimum Specifications for Battery Systems topic.

Three-phase system with three Sol-Ark 15K-2P-N inverters and two HELIOS ESS 52-48-16000 batteries

  • For a three-phase system set to the lessor value between the master inverter’s maximum charge rate or the master inverter, or the quantity of attached batteries multiplied by the battery’s maximum charge rating divided by the number of inverters. For example, set the 12K-2P-N inverter to the lessor of the inverter’s maximum charge rate of 185 A, or 133 A for two HELIOS ESS 52-48-16000 batteries that are each rated at a maximum charge of 200 A, and then divided by three inverters (2 x 200 A ÷ 3 = 133.33 A).

Max A Discharge

For a single inverter, set to the lesser value between the inverter’s maximum discharge rate or the quantity of attached batteries multiplied by the battery’s maximum discharge rating. For example, set the 12K-2P-N inverter to the lesser of the inverter’s maximum discharge rate of 185 A, or 380 A for two HELIOS ESS 52-48-16000 batteries.

  • NOTE: Each HELIOS ESS battery is rated at a 200 A discharge rate, but when connected in parallel, the maximum current is limited by internal busbars. For the recommended maximum current for paralleled HELIOS ESS, refer to the table in the Minimum Specifications for Battery Systems topic.

For a three-phase system, set to the lesser value between the master inverter’s maximum discharge rate or the quantity of attached batteries multiplied by the battery’s maximum discharge rating divided by the number of inverters. For example, set the 12K-2P-N inverter to the lesser of the inverter’s maximum discharge rate of 185 A, or 133 A for two HELIOS ESS 52-48-16000 batteries that are each rated at a maximum discharge rate of 200 A and then divided by 3 inverters (2 x 200 A ÷ 3 = 133.33 A).

TEMPCO

Set to 0 mv/C/Cell. Discover Lithium batteries do not require temperature compensation.

Use Batt V Charged

Enable

Use Batt % Charged

Disable

BMS Lithium Batt

Disable

Activate Battery

Enable

Open Loop: System Setup > Battery Setup > Charge

Open Loop Charge.png

Battery Setting - Sol-Ark Open-loop Battery Settings

Batt Setup > Charge

StartV

Set to user preference based on battery voltage. The recommended minimum is 48 V.

Start%

Unavailable (Grey) in an open-loop configuration.

Float V

53.6 V

Absorption V

55.2 V

Equalization V

Do not equalize Discover Lithium batteries.

Equalization Days

Equalization Hours

Open Loop: System Setup > Battery Setup > Discharge

Open Loop Discharge.png

Battery Setting - Sol-Ark Open-loop Battery Settings

Batt Setup > Discharge

Shutdown

Adjust values to support the use case or keep the original values.

Low Batt

Restart

Batt Empty V

48 V

Batt Resistance

Set to: 10 mOhm divided by the number of batteries (plus the mOhm value for cable resistance, if known).

Batt Charge Efficiency

98%

BMS_Err_Stop

Clear this check box in an open-loop configuration.

NOTE

For more information about configuring the Sol-Ark inverter-charger, refer to product documentation on Sol-Ark website (sol-ark.com) or the LYNK II Installation and User Manual (805-0033).

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.