805-0091 HELIOS ESS Sol-Ark Conduit Box Manual

Wiring

caution.png

FIRE HAZARD

  • Undersized fuses and disconnects may become overloaded and potentially cause a fire.

  • Fuses and disconnects are required to open before the cable reaches its maximum current-carrying capability.

Failure to follow these instructions may result in injury.

caution.png

ELECTRIC SHOCK AND FIRE HAZARD

  • Take precautions to avoid bridging the terminals.

  • Do not contact the terminals with metal mountings, fixtures, or body parts.

Failure to follow these instructions may result in injury.

NOTE

  • The Sol-Ark 15K-2P-N hybrid inverter requires two positive and two negative 2/0 AWG cables, as specified in the Sol-Ark documentation.

    • The HELIOS ESS Battery to Inverter Power Cables (950-0070), with two sets of positive and negative 2/0 AWG cables, satisfy Sol-Ark’s requirement for the battery to inverter cables.

Refer to the HELIOS ESS Installation and Operation Manual (805-0090) and the LYNK II Sol-Ark User Manual (805-0038) for information on wiring and configuring the batteries and inverter.