There are two standard inverter-to-cabinet configurations.
-
1 Inverter: 1 Cabinet
One Sol-Ark Inverter, One AES Cabinet -
1 Inverter: 2 Cabinets
One Sol-Ark Inverter, Two AES Cabinets
Systems can scale up to 10 Sol-Ark inverters in parallel on the AC bus, supporting total outputs of up to 300 kW (30K), 600 kW (60K), or 1,000 kW (100K).
When designing larger systems, maintain consistent inverter-to-cabinet ratios across the entire installation. For example, if your system starts with a 1:1 ratio (one inverter per cabinet), all additional inverter-cabinet sets should follow the same 1:1 pattern.
|
NOTICE |
|---|
|
UNBALANCED BATTERY HAZARD Mixing ratios within the same system (e.g., combining 1:1 and 1:2 configurations) is not supported, as it can lead to unbalanced load sharing. Failure to observe these ratios will result in underutilization of the battery system. |