As a precautionary measure, it is recommended to program the Sol-Ark inverter with the correct voltage-based open-loop parameters before setting up closed-loop parameters.
If necessary, first configure Sol-Ark inverters to operate in parallel by establishing the inverter master/slave relationships and phase designations before setting the parameters for battery operation. Configuring the master inverter will cascade parameters and settings to the slave inverters.
The Open-loop Configuration Procedure
Refer to the latest Discover Energy Systems documentation for battery values and the latest Sol-Ark documentation for details on menu navigation and the setup procedure.
-
Set the Discover Lithium batteries to ON and set the inverter to ON.
-
Using the touch screen and keypad on the inverter, navigate from the SYSTEM SETUP menu to the BATT SETUP menu screen.
-
Enable and disable parameters according to the instructions in the tables below.
-
Set each variable parameter according to the instructions in the tables below.
-
Touch the OK button to save all onscreen values - Ignore data displayed in GREY boxes.
|
NOTE |
|---|
|
Touch the Sol-Ark screen to:
Values are adjusted using the keypad. |
|
NOTE |
|---|
|
Enable parameters with a CHECKMARK, and disable parameters by leaving them unchecked. Touch a WHITE box onscreen to activate the adjustment of that value. Selecting parameters that have been enabled and disabled alters values that are available to be adjusted.
|
|
NOTE |
|---|
|
If necessary, configure Sol-Ark inverters to operate in parallel before setting the parameters for battery operation. |