NOARK Self-Managed (Open-Loop) Configuration

If managed (closed-loop) communication cannot be established, the NOARK inverter-charger will need to be manually converted to a self-managed (open-loop) configuration. For battery values, refer to the latest Discover Lithium battery documentation. For details on menu navigation and the setup procedure, refer to the latest NOARK documentation.

  1. Set the Discover Lithium batteries to ON and set the inverter-charger to ON.

  2. Using the touch screen and keypad on the inverter, navigate to Main Screen > System Setup > Battery Setting.

  3. Specify the battery settings according to the instructions in the tables that follow. Touch the Up and Down arrows to scroll through screens.

  4. Touch the check mark button to save changes.

  5. Exit and restart the inverter-charger.

NOTE

If using multiple inverter-chargers, configure NOARK inverter-chargers to operate in parallel before setting the parameters for battery operation.