E-Stop/Bladed Lockable Disconnect

AES RACKMOUNT Lithium batteries are connected with an inverter in the following E-stop/bladed lockable disconnect circuits (Figure 6, Figure 7). An emergency switch that is normally closed is connected to the RPO terminals in the system, allowing communication until the switch is engaged.

In an emergency, push down on the E-stop button or pull the handle of the bladed lockable disconnect to open (disconnect) the communication circuit and turn off the batteries.

NOTE

  • Apply the E-stop/bladed lockable disconnect circuit identified in this document to one RPO board only.

  • To connect the maximum 36 AES RACKMOUNT batteries with the E-stop/bladed lockable disconnect circuit, do not connect communication cables (CAT6 or higher) to the RJ45 ports of the RPO board on more than one Slimline Enclosure or Battery Module Combiner Box.

  • To connect the maximum 36 AES RACKMOUNT batteries, they must be set up with firmware version 4.6 or later.