Skip to main content
Skip table of contents

Minimum Battery System Capacity

The Discover Lithium Battery and Solis device automatically manage the battery charge and discharge rates. Using large solar arrays with battery banks that are too small can exceed the operating limits of the battery to charge and possibly lead to the BMS triggering over-current protection. Battery capacity must accept the maximum charge current of the system, or charging must be curtailed below the operating limit of the installed batteries. Derive this value by adding together the charge capacities of all inverter-chargers and solar charge controllers in the system. Additionally, battery peak capacity must support the surge requirements demanded by the load attached to the inverter. Match all inverter peak power values with the sum of all battery peak current values.

Inverter Peak = (Inverter Surge Value) / (Inverter Efficiency) / (48V: Low Battery Cut-Off)

 

Single-Phase Models

Inverter Peak (10 seconds) (1)

 

Max

Continuous

Charge

Max

Continuous

Discharge

AES RACKMOUNT
48-48-5120 /
48-48-5120-H
Minimum per inverter (2)

HELIOS ESS
52-48-16000
Minimum per inverter (3)

S6-EH2P9.6K03-SV-YD-L-US

416 A

200 A

200 A

3

2

S6-EH2P11.4K03-SV-YD-L-US

494 A

237.5 A

237.5 A

3

2

S6-EH2P12K03-SV-YD-L-US

520 A

250 A

250 A

3

2

S6-EH2P14K03-SV-YD-L-US

607 A

290 A

290 A

4

2

S6-EH2P16K03-SV-YD-L-US

694 A

290 A

290 A

4

3

(1) Calculated based on 2X rated output power in the Solis Split Phase Low Voltage Energy Storage Inverters S6-EH2P(9.6-16)K03-SV-YD-L-US.

(2) Discover AES RACKMOUNT 48-48-5120/48-48-5120-H Battery, Peak Power (3 seconds): 218 A RMS, 95 A DC Continuous Charge/Discharge (1 hour), as published in Discover AES RACKMOUNT Installation and Operation Manual (805-0043 Rev J).

(3) Discover HELIOS ESS 52-48-16000 Battery, Peak Discharge Current (15 seconds): 300 A RMS, 200 A Continuous Charge/Discharge, as published in Discover HELIOS ESS Installation and Operation Manual (805-0090 Rev D).