OVERVIEW AND TEST PREPARATION
Purpose
The SAT focuses on performance and functional testing of the energy storage system. Either the supplier or a qualified service operator must complete the SAT.
Products
The SAT applies to the AES CABINET line of products.
Description | |||||
|---|---|---|---|---|---|
Unit Model Number | SLL03C2-D1P52S1R4-A01 | SLL03C2-D1P52S1R5-A01 | SLL03C2-D1P52S1R6-A01 | SLL03C2-D1P52S1R7-A01 | SLL03C2-D1P52S1R8-A01 |
Model | 212-CAB | 266-CAB | 318-CAB | 372-CAB | 426-CAB |
References
Test requirement references
NFPA 55: Implement the AES Cabinet System Annual Test in conjunction with NFPA 55 acceptance testing.
Test Environment
Cabinet
Temperature: 20 to 30ºC (68 to 86ºF)
Relative Humidity: 5 to 100%
Electrical Environment
Main circuit voltage: 220 to 277 Vac
Main circuit frequency: 60±0.5 or 50±0.5 Hz
SAT Test Equipment
The required testing tools include, but are not limited to, the items in the following table.
Tool | Example |
|---|---|
SDI Smoke Detector Tester
| ![]() |
Heat Gun or Hair dryer (≥63°C or 145 F)
| ![]() |
Laptop (Windows 11)
| ![]() |
Multimeter
| ![]() |