805-0033 LYNK II Installation Manual

Minimum Battery System Capacity

The Discover Lithium Battery and Schneider Electric device automatically manage the battery charge and discharge rates. Using large solar arrays with battery banks that are too small can exceed the operating limits of the battery to charge and possibly lead to the BMS triggering over-current protection. Battery capacity must accept the maximum charge current of the system, or charging must be curtailed below the operating limit of the installed batteries. Derive this value by adding together the charge capacities of all inverter-chargers and solar charge controllers in the system. Additionally, battery peak capacity must support the surge requirements demanded by the load attached to the inverter-charger. Match all inverter-charger peak power values with the sum of all battery peak current values.

Inverter Peak = (Inverter Surge Value) / (Inverter Efficiency) / (48V: Low Battery Cut-Off)

Model

Inverter Peak
(60 seconds)

Max Continuous Charge

Max Continuous Discharge

AES RACKMOUNT 48-48-5120

Recommended per inverter (8)

HELIOS ESS 52-48-16000

Recommended per inverter (9)

XW PRO

6848 NA 120/240

276 A (1)

140 A

180 A

2

1

6848 NA 120

278 A (2)

120 A

180 A

2

1

8548 IEC 230

267 A (3)

140 A

180 A

2

1

XW+

5548 NA 120/240

220 A (4)

110 A

150 A

2

1

6848 NA 120/240

281 A (5)

140 A

180 A

2

1

7048 E 230

200 A (6)

110 A

150 A

2

1

8548 E 230

265 A (7)

140 A

180 A

2

1

(1) Calculated based on max 180 A DC input, 52 A at 240 VAC 60-second output, efficiency 94.1% (CEC), and 140 A DC charger, as published in Schneider Electric data sheets (2022-06).

(2) Calculated based on 180 A DC input, 104 A at 120 VAC 60-second output, efficiency 93.6% (CEC), and 120 A DC charger, as published in Schneider Electric data sheets (2022-06).

(3) Calculated based on max 180 A DC input, 53 A at 230 VAC 60-second output, efficiency 95% (Peak), and 140 A DC charger, as published in Schneider Electric data sheets (2022-06).

(4) Calculated based on max 150 A DC input, 41 A at 240 VAC 60-second output, efficiency 92.5% (CEC), and 110 A DC charger, as published in Schneider Electric data sheets (2017-09).

(5) Calculated based on max 180 A DC input, 52 A at 240 VAC 60-second output, efficiency 93% (CEC), and 140 A DC charger, as published in Schneider Electric data sheets (2017-09).

(6) Calculated based on max 150 A DC input, 40 A at 230 VAC 60-second output, efficiency 95.8% (Peak), and 110 A DC charger, as published in Schneider Electric data sheets (2017-09).

(7) Calculated based on max 180 A DC input, 53 A at 230 VAC 60-second output, efficiency 95.8% (Peak), and 140 A DC charger, as published in Schneider Electric data sheets (2017-09).

(8) Discover AES RACKMOUNT 48-48-5120/48-48-5120-H Battery, Peak Power: 218 A RMS (3 seconds), 95 A DC Continuous Charge/Discharge, as published in Discover AES RACKMOUNT Installation and Operation Manual (805-0043).

(9) Discover HELIOS ESS Battery, Peak Discharge Current: 300 A RMS (15 seconds), 200 A DC Max Continuous Charge/Discharge, as published in Discover HELIOS ESS Installation and Operation Manual (805-0090).