STORAGE
Leaving the battery connected to a trickle load or power electronics will cause the battery to discharge during storage. Without any load, the battery will self-discharge by approximately 3.5% per month while in storage. After storage, charge the battery to 100% SOC and perform at least one full discharge and charge cycle before returning the battery to service.
Store at 95% SOC or more. To store the battery for up to 6 months, store the battery at 95% SOC or more. It must remain disconnected from all loads and power electronics during storage.
Switch OFF the battery. Set the battery to OFF.
Check SOC every six months. Recharge the battery to above 95% SOC every six months.
Proper storage temperature. Ensure storage is within the temperatures specified below.
1 Month storage temperature -20°C to 55°C (-4°F to 131°F)
6 Month storage temperature -10°C to 30°C (14°F to 86°F)
NOTICE |
|---|
VOID WARRANTY
Failure to follow these instructions may result in equipment damage. |
NOTICE |
|---|
BATTERY DAMAGE