HELIOS ESS |
Description |
|---|---|
|
Battery model number |
52-48-16000 (900-0077) |
|
Maximum capacity per unit |
16 kWh |
|
Minimum separation from other ESS (sides) |
25.4 mm (1.0 in) |
|
Minimum separation from other ESS (front to back) |
25.4 mm (1.0 in) |
|
Minimum separation from other ESS (above/below) |
Not applicable (1) |
|
Minimum separation from combustible build constructions and other structures |
25.4 mm (1.0 in) |
|
Exterior wall minimum separation from other ESS (side to side) |
25.4 mm (1.0 in) |
|
Exterior wall minimum separation from other ESS (above/below) |
Not applicable (1) |
|
Exterior wall minimum separation from other openings |
91.4 cm (36 in) |
|
UL 9540 Edition |
UL 9540:2023 (3rd Edition DC Energy Storage System) Report CN2549VH 001 The UL9540 certification applies when paired with any UL1741-listed inverter. |
|
UL9540A Testing Organization, Report, Date |
UL 9540A:2019 (Fourth Edition), Module Level Report CN248DTM 002
|
|
Additional fire suppression required |
None |
|
Additional explosion protection |
Minimum compliant room size is 32.5 m3 (1,148 ft3) (2)(3) |
|
Other limitations |
Listed for indoor or outdoor, residential and non-residential use. Units for residential applications are intended to be installed in attached or detached garages, sheds, enclosed utility closets, basements, storage, or utility spaces within a dwelling. It is not intended for installation in habitable living spaces or dwelling areas. |
|
Suitable for habitable spaces of dwellings? |
No |
|
Suitable locations |
Residential, non-residential (4) (indoor, outdoor) |
|
Limited access requirements |
None |
|
Environmental restrictions |
Not suitable in locations exposed to salt spray, humid marine environments, or condensation. |
|
Emergency Service Contact information |
Infotrac: 1-800-535-5053 (Account # 115375) |
|
DC ESS |
The electrical ratings of connected power conversion equipment shall be compatible with Electrical Specifications. |
|
Residential smoke or heat alarm required? |
Yes, when installed indoors as per local code. |
(1) There is no limitation to installing a HELIOS ESS battery above or below other HELIOS ESS.
(2) The room volume protects against explosion in the unlikely event of a battery releasing explosive gases and entering thermal runaway. In normal operation, LiFePO4 batteries do not release any hazardous gas. If the room has a 9 ft ceiling, 1,148 ft3 equates to a minimum room size of 10 x 13 ft. Room sizing does not increase if installing more than one battery.
(3) If the room is smaller than prescribed, adding vents, deflagration vents, or a constantly running air circulation system could reduce the required room size. A certified safety engineer should determine the venting and volume of air circulation required.
(4) UL9540A definitions for residential and non-residential use.
-
NON-RESIDENTIAL USE – Intended for use in commercial, industrial, or utility-owned locations.
-
RESIDENTIAL USE – In accordance with this standard, intended for use in one or two-family homes, town homes, and individual dwelling units of multi-family dwellings.