AES 210HV Cabinet Electrical Specifications
|
Electrical Specifications |
AES 210HV |
|---|---|
|
Chemistry |
LiFePO4 (LFP) |
|
Nominal Voltage |
665.6 V |
|
Cabinet Battery Pack Configuration |
4 Packs |
|
Nominal Energy |
213 kWh |
|
Usable Energy |
209 kWh |
|
Nominal Capacity |
320 Ah |
|
Usable Capacity |
314 Ah |
|
BMS High Voltage Shutdown |
759.2 V |
|
Charge Voltage Stop |
748.8 V |
|
Charge Voltage Limit |
738.4 V |
|
Discharge Voltage Limit |
603.2 V |
|
Discharge Voltage Stop |
582.4 V |
|
BMS Low Voltage Shutdown |
540.8 V |
|
Maximum Continuous Current |
157 A |
|
Maximum Current |
200 A |
|
DC Over Current Protection |
315 A fuses (+/-) |
|
AC Input Protection |
32 A 2P Breaker |
|
Maximum short circuit fault current (IBF / ½ IBF) |
9900 A (1.28 ms) / 4950 A (1.28 ms) |
|
Arc Flash Incident Energy IEm |
0.1371 Cal/cm2 |
|
Arc Flash Protection Boundary (AFB) |
165 mm / 6.496 in |
AES 210HV Battery Pack Electrical Specifications
|
Electrical Specifications |
AES 210HV / SLL03C2-D1P52S1R4-A01 |
|---|---|
|
Pack model |
PLL03C2-D1P52S-A01 |
|
Cell model |
GSP71173204F, 3.2 V 320 Ah |
|
Series and parallel |
1P52S |
|
Nominal capacity |
320 Ah |
|
Nominal energy |
53.25 kWh |
|
Nominal voltage |
166.4 Vdc |
|
Maximum working voltage range |
130 to 189.8 Vdc |
|
Maximum charge current |
173 A @ 25°C (77°F) |
|
Maximum discharge current |
173 A @ 25°C (77°F) |
|
Energy Density |
≥ 174 Wh/kg |
|
Standard charge/discharge |
C/2 @ STC |
|
Rated charge/discharge current |
157 A |
|
Cooling Method |
Active Liquid Cooling |
|
All values represented above are based on STC: 25°C ±5°C (77°F ±9°F); 0.5 C; DOD 100%; 2.5V to 3.65V/cell |
|