805-0033 LYNK II Installation Manual

Setting Closed-Loop Configuration

Refer to the latest Discover Energy Systems documentation for battery values and the
latest Victron documentation for menu navigation and details on the setup procedure.

  1. Set the Discover Lithium batteries to ON and the Victron GX device to ON.

  2. Using a touch screen or other user interface of the GX device, set the VE.Can
    port and CAN-Bus BMS communication rate to 250 kbit/s to match the
    communication speed set up on the LYNK II communication gateway.

Device List > Settings > Services > VE.Can port > CAN-bus profile
• Select VE.Can & CAN-bus BMS (250 kbit/s)
(Select Victron solar inverters may operate with CAN-bus BMS 500 kbit/s)

image-20250513-221436.png

CAN-bus profile

  1. Return to the Device List, and the Discover Lithium Battery should now appear
    as one of the devices.

Device List

image-20250513-221557.png

Device List

NOTE

If Discover does not appear on the Device List, confirm that the CAT5e or higher communication cable is a normal patch type, not a cross-over type. Use manufactured cables to avoid bad crimps and reduce the risk of a poor connection.

  1. To confirm that all batteries in the network are communicating with the Victron system, review the actual battery parameters. If multiple batteries are connected, a single entry shows the total limit of all the batteries.

Device List > Discover AES > Parameters

image-20250514-182804.png

Battery Parameters

Closed-loop Settings

During normal operation, the battery’s charge parameter limits are set by the BMS and communicated by the Victron GX device to the inverter-charger and MPPT.

To optimize the performance of a Victron system, manually set the following DVCC menu items using the Victron GX device and reboot the system.

Device List > Settings > DVCC

image-20250514-183511.png

DVCC Menus 1/2

image-20250514-183610.png

DVCC Menus 2/2

DVCC Menu

Setting

DVCC (Distributed Voltage and Current Control)

Forced on

Limit charge current

ON (1)

Maximum charge current

Installed number of Discover Lithium batteries x their rated Maximum Charge current, or a lower value if system curtailment is required.

Limit managed battery charge voltage

Disable

SVS - Shared voltage sense

Forced off (2)

STS - Shared temperature sense

Forced off

SCS - Shared current sense

ON

SCS status

(Displays the current status)

Controlling BMS

Automatic Selection

(1) Limit charge current works across the whole system. MPPTs are automatically prioritized over the mains. In cases where the BMS requests a maximum charge current different from the user-configurable setting, it uses the lesser of the two.

(2) SVS should be set to OFF (Victron support has reported instances of conflicts when SVS is set to ON with a Lithium BMS).

Saving Closed-Loop Settings

Device List > Settings > General > Reboot?

After all DVCC menu items have been set, reboot the system to complete the closed-loop configuration.

image-20250514-183940.png

Rebooting the System

NOTE

To avoid conflicting network information and data, do not use a Victron BMV battery monitor when using the LYNK II Communication Gateway.