Skip to main content
Skip table of contents

Appendix 1. Battery Cabinet Data

NOTE

The following data can only be accessed by the read function code 0x03.

REGISTER ADDRESS

DATA TYPE

DATA DESCRIPTION

DATA UNIT

COMMENTS

1001

UINT16

Total cabinet voltage

0.1 V

1002

UINT16

Cabinet bus current

0.1 A

Offset + 32000

1003

UINT16

Cabinet SOC

0.1 %

1004

UINT16

Cabinet SOH

0.1 %

1005

UINT16

Positive insulation resistance of cabinet

1006

UINT16

Negative insulation resistance of cabinet

1007

UINT16

Highest cell voltage pack number

1008

UINT16

Max cell voltage BMU No

1009

UINT16

Serial number of the highest cell voltage in pack (box)

1010

UINT16

Max cell voltage

mv

1011

UINT16

Lowest cell voltage pack number

1012

UINT16

Min cell voltage BMU No

1013

UINT16

Serial number of the lowest cell voltage in pack

1014

UINT16

Min cell voltage

mv

1015

UINT16

Max cell temperature, pack number

1016

UINT16

Max cell temperature, BMU No

1017

UINT16

Max cell temperature, box serial number

1018

UINT16

Max cell temperature

°C +40°C

1019

UINT16

Lowest cell temperature, pack number

1020

UINT16

Min cell temperature BMU No

1021

UINT16

Min cell temperature, box serial number

1022

UINT16

Min cell temperature

°C +40°C

1023

UINT16

Max cell voltage difference

mv

1024

UINT16

Max cell differential voltage, pack number

1025

UINT16

Max temperature difference

°C

1026

UINT16

Max temperature difference, pack number

1027

UINT16

Max pack bus voltage

0.1 V

1028

UINT16

Max pack bus voltage, pack number

1029

UINT16

Min pack bus voltage

0.1 V

1030

UINT16

Min pack bus voltage, pack number

1031

UINT16

Max bus differential voltage

0.1 V

1032

UINT16

Max pack SOC value

0.1 %

1033

UINT16

Max SOC pack number

1034

UINT16

Min pack SOC value

0.1 %

1035

UINT16

Min SOC pack number

1036

UINT16

Number of sbcu packs in the cabinet

Real-time data

1037

UINT16

Number of sbmu in pack

1038

UINT16

Number of cells in sbmu

1039

UINT16

Cumulative number of temperatures in sbmu

1040

UINT16

Max limit current for cabinet charging

0.1 A

1041

UINT16

Max limiting current for cabinet discharge

0.1 A

1042

UINT16

Charge/discharge times

1043

UINT16

Charge energy in cabinet for the day

0.1 kWh

1044

UINT16

Discharge energy in cabinet for current day

0.1 kWh

1045

UINT16

Chargeable energy in cabinet

0.1 kWh

1046

UINT16

Dischargeable energy in cabinet

0.1 kWh

1047

UINT32

Cumulative charging energy of cabinet

0.1 kWh

1049

UINT32

Cumulative discharge energy of cabinet

0.1 kWh

1051

UINT16

Cabinet SOE

0.1 %

JavaScript errors detected