NOTE |
|---|
|
The following data can only be accessed by the read function code |
|
REGISTER ADDRESS |
DATA TYPE |
DATA DESCRIPTION |
DATA UNIT |
COMMENTS |
|---|---|---|---|---|
|
1001 |
UINT16 |
Total cabinet voltage |
0.1 V |
|
|
1002 |
UINT16 |
Cabinet bus current |
0.1 A |
Offset + 32000 |
|
1003 |
UINT16 |
Cabinet SOC |
0.1 % |
|
|
1004 |
UINT16 |
Cabinet SOH |
0.1 % |
|
|
1005 |
UINT16 |
Positive insulation resistance of cabinet |
KΩ |
|
|
1006 |
UINT16 |
Negative insulation resistance of cabinet |
KΩ |
|
|
1007 |
UINT16 |
Highest cell voltage pack number |
|
|
|
1008 |
UINT16 |
Max cell voltage BMU No |
|
|
|
1009 |
UINT16 |
Serial number of the highest cell voltage in pack (box) |
|
|
|
1010 |
UINT16 |
Max cell voltage |
mv |
|
|
1011 |
UINT16 |
Lowest cell voltage pack number |
|
|
|
1012 |
UINT16 |
Min cell voltage BMU No |
|
|
|
1013 |
UINT16 |
Serial number of the lowest cell voltage in pack |
|
|
|
1014 |
UINT16 |
Min cell voltage |
mv |
|
|
1015 |
UINT16 |
Max cell temperature, pack number |
|
|
|
1016 |
UINT16 |
Max cell temperature, BMU No |
|
|
|
1017 |
UINT16 |
Max cell temperature, box serial number |
|
|
|
1018 |
UINT16 |
Max cell temperature |
°C +40°C |
|
|
1019 |
UINT16 |
Lowest cell temperature, pack number |
|
|
|
1020 |
UINT16 |
Min cell temperature BMU No |
|
|
|
1021 |
UINT16 |
Min cell temperature, box serial number |
|
|
|
1022 |
UINT16 |
Min cell temperature |
°C +40°C |
|
|
1023 |
UINT16 |
Max cell voltage difference |
mv |
|
|
1024 |
UINT16 |
Max cell differential voltage, pack number |
|
|
|
1025 |
UINT16 |
Max temperature difference |
°C |
|
|
1026 |
UINT16 |
Max temperature difference, pack number |
|
|
|
1027 |
UINT16 |
Max pack bus voltage |
0.1 V |
|
|
1028 |
UINT16 |
Max pack bus voltage, pack number |
|
|
|
1029 |
UINT16 |
Min pack bus voltage |
0.1 V |
|
|
1030 |
UINT16 |
Min pack bus voltage, pack number |
|
|
|
1031 |
UINT16 |
Max bus differential voltage |
0.1 V |
|
|
1032 |
UINT16 |
Max pack SOC value |
0.1 % |
|
|
1033 |
UINT16 |
Max SOC pack number |
|
|
|
1034 |
UINT16 |
Min pack SOC value |
0.1 % |
|
|
1035 |
UINT16 |
Min SOC pack number |
|
|
|
1036 |
UINT16 |
Number of sbcu packs in the cabinet |
|
Real-time data |
|
1037 |
UINT16 |
Number of sbmu in pack |
|
|
|
1038 |
UINT16 |
Number of cells in sbmu |
|
|
|
1039 |
UINT16 |
Cumulative number of temperatures in sbmu |
|
|
|
1040 |
UINT16 |
Max limit current for cabinet charging |
0.1 A |
|
|
1041 |
UINT16 |
Max limiting current for cabinet discharge |
0.1 A |
|
|
1042 |
UINT16 |
Charge/discharge times |
|
|
|
1043 |
UINT16 |
Charge energy in cabinet for the day |
0.1 kWh |
|
|
1044 |
UINT16 |
Discharge energy in cabinet for current day |
0.1 kWh |
|
|
1045 |
UINT16 |
Chargeable energy in cabinet |
0.1 kWh |
|
|
1046 |
UINT16 |
Dischargeable energy in cabinet |
0.1 kWh |
|
|
1047 |
UINT32 |
Cumulative charging energy of cabinet |
0.1 kWh |
|
|
1049 |
UINT32 |
Cumulative discharge energy of cabinet |
0.1 kWh |
|
|
1051 |
UINT16 |
Cabinet SOE |
0.1 % |
|