Appendix 3. Battery Pack Statistics
Offset address P = 1300 + 100 * n (n represents the number of packs, 0 ≤ n < 32, n = 0 represents the first pack)
NOTE |
|---|
The following data can only be accessed by the read function code |
PROCESSOR REGISTER ADDRESS | DATA TYPE | DATA DESCRIPTION | DATA UNIT | COMMENTS |
|---|---|---|---|---|
P+1 | UINT16 | Total Pack Voltage | 0.1 V |
|
P+2 | UINT16 | Total Pack Current | 0.1 A | |
P+3 | UINT16 | Pack SOC | 0.1 % |
|
P+4 | UINT16 | Pack SOH | 0.1 % |
|
P+5 | UINT16 | Pack insulation positive resistance | KΩ |
|
P+6 | UINT16 | Pack insulation negative resistance | KΩ |
|
P+7 | UINT16 | Max cell voltage BMU No |
|
|
P+8 | UINT16 | Serial number of the highest cell voltage in pack |
|
|
P+9 | UINT16 | Max cell voltage | mv |
|
P+10 | UINT16 | Min cell voltage BMU No |
| |
P+11 | UINT16 | Serial number of the lowest cell voltage in pack |
|
|
P+12 | UINT16 | Min cell voltage | mv |
|
P+13 | UINT16 | Max cell temperature, BMU No |
|
|
P+14 | UINT16 | Max cell temperature, box serial number |
| |
P+15 | UINT16 | Max cell temperature | °C +40°C | Real data +40°C |
P+16 | UINT16 | Min cell temperature, BMU No |
| |
P+17 | UINT16 | Min cell temperature, box serial number |
|
|
P+18 | UINT16 | Min cell temperature | °C +40°C | Real data +40°C |
P+19 | UINT16 | Max cell voltage difference | mv |
|
P+20 | UINT16 | Average cell voltage |
| |
P+21 | UINT16 | Max temperature difference | °C |
|
P+22 | UINT16 | Average temperature | °C +40°C | Real data +40°C |
P+23 | UINT16 | Charging current limit | 0.1 A |
|
P+24 | UINT16 | Discharge current limit | 0.1 A |
|
P+25 | UINT16 | Pack charge/discharge cycles |
| |
P+26 | UINT16 | Single charge energy | 0.1 kWh |
|
P+27 | UINT16 | Single discharge energy | 0.1 kWh |
|
P+28 | UINT32 | Cumulative Pack charging energy | 0.1kWh |
|
P+30 | UINT32 | Cumulative Pack discharge capacity | 0.1 kWh |
|
P+32 | UINT16 | Pack number | 0.1 kWh |
|