NOTE |
|---|
|
The following data can be accessed by the read function code |
|
REGISTER ADDRESS |
DATA TYPE |
DATA DESCRIPTION |
DATA UNIT |
COMMENTS |
|---|---|---|---|---|
|
50001 |
UINT16 |
Level 1 single cell max voltage alarm |
mv |
|
|
50002 |
UINT16 |
Level 2 single cell max voltage alarm |
mv |
|
|
50003 |
UINT16 |
Level 3 single cell max voltage alarm |
mv |
|
|
50004 |
UINT16 |
Single cell max voltage alarm return value |
mv |
|
|
50005 |
UINT16 |
Level 1 single cell low voltage alarm |
mv |
|
|
50006 |
UINT16 |
Level 2 single cell low voltage alarm |
mv |
|
|
50007 |
UINT16 |
Level 3 single cell low voltage alarm |
mv |
|
|
50008 |
UINT16 |
Single cell low voltage alarm return value |
mv |
|
|
50009 |
UINT16 |
Level 1 single cell large differential alarm |
mv |
|
|
50010 |
UINT16 |
Level 2 single cell large differential alarm |
mv |
|
|
50011 |
UINT16 |
Level 3 single cell large differential alarm |
mv |
|
|
50012 |
UINT16 |
Single cell large differential voltage alarm return value |
mv |
|
|
50013 |
UINT16 |
Level 1 Total cell high voltage alarm |
0.1 V |
|
|
50014 |
UINT16 |
Level 2 Total cell high voltage alarm |
0.1 V |
|
|
50015 |
UINT16 |
Level 3 Total cell high voltage alarm |
0.1 V |
|
|
50016 |
UINT16 |
Total cell high voltage alarm return value |
0.1 V |
|
|
50017 |
UINT16 |
Level 1 Total cell low voltage alarm |
0.1 V |
|
|
50018 |
UINT16 |
Level 2 Total cell low voltage alarm |
0.1 V |
|
|
50019 |
UINT16 |
Level 3 Total cell low voltage alarm |
0.1 V |
|
|
50020 |
UINT16 |
Total cell low voltage alarm return value |
0.1 V |
|
|
50021 |
UINT16 |
Level 1 High discharge current alarm |
0.1 A |
|
|
50022 |
UINT16 |
Level 2 High discharge current alarm |
0.1 A |
|
|
50023 |
UINT16 |
Level 3 High discharge current alarm |
0.1 A |
|
|
50024 |
UINT16 |
High discharge current alarm return value |
0.1 A |
|
|
50025 |
UINT16 |
Level 1 High charge current alarm |
0.1 A |
|
|
50026 |
UINT16 |
Level 2 High charge current alarm |
0.1 A |
|
|
50027 |
UINT16 |
Level 3 High charge current alarm |
0.1 A |
|
|
50028 |
UINT16 |
High charge current alarm return value |
0.1 A |
|
|
50029 |
UINT16 |
Level 1 Low insulation alarm |
kΩ |
|
|
50030 |
UINT16 |
Level 2 Low insulation alarm |
kΩ |
|
|
50031 |
UINT16 |
Level 3 Low insulation alarm |
kΩ |
|
|
50032 |
UINT16 |
Low insulation alarm return value |
kΩ |
|
|
50033 |
UINT16 |
Level 1 Charging high temperature alarm |
°C, +40 |
BMS sends with real data +40°C |
|
50034 |
UINT16 |
Level 2 Charging high temperature alarm |
°C, +40 |
BMS sends with real data +40°C |
|
50035 |
UINT16 |
Level 3 Charging high temperature alarm |
°C, +40 |
BMS sends with real data +40°C |
|
50036 |
UINT16 |
Charging high temperature return value |
°C |
|
|
50037 |
UINT16 |
Level 1 Charging low temperature alarm |
°C, +40 |
BMS sends with real data +40°C |
|
50038 |
UINT16 |
Level 2 Charging low temperature alarm |
°C, +40 |
BMS sends with real data +40°C |
|
50039 |
UINT16 |
Level 3 Charging low temperature alarm |
°C, +40 |
BMS sends with real data +40°C |
|
50040 |
UINT16 |
Charging low temperature return value |
°C |
|
|
50041 |
UINT16 |
Level 1 Discharge high temperature alarm |
°C, +40 |
Real data +40°C when sent by BMS |
|
50042 |
UINT16 |
Level 2 Discharge high temperature alarm |
°C, +40 |
Real data +40°C when sent by BMS |
|
50043 |
UINT16 |
Level 3 Discharge high temperature alarm |
°C, +40 |
Real data +40°C when sent by BMS |
|
50044 |
UINT16 |
Discharge high temperature alarm return value |
°C |
|
|
50045 |
UINT16 |
Level 1 Discharge low temperature alarm |
°C, +40 |
Real data +40°C when sent by BMS |
|
50046 |
UINT16 |
Level 2 Discharge low temperature alarm |
°C, +40 |
Real data +40°C when sent by BMS |
|
50047 |
UINT16 |
Level 3 Discharge low temperature alarm |
°C, +40 |
Real data +40°C when sent by BMS |
|
50048 |
UINT16 |
Discharge low temperature alarm return value |
°C |
|
|
50049 |
UINT16 |
Level 1 High temperature difference alarm |
°C |
|
|
50050 |
UINT16 |
Level 2 High temperature difference alarm |
°C |
|
|
50051 |
UINT16 |
Level 3 High temperature difference alarm |
°C |
|
|
50052 |
UINT16 |
High temperature difference alarm return value |
°C |
|
|
50053 |
UINT16 |
Level 1 Low SOC alarm |
0.1 % |
|
|
50054 |
UINT16 |
Level 2 Low SOC alarm |
0.1 % |
|
|
50055 |
UINT16 |
Level 3 Low SOC alarm |
0.1 % |
|
|
50056 |
UINT16 |
Low SOC alarm return value |
0.1 % |
|
|
50057 |
UINT16 |
Level 1 High SOC alarm |
0.1 % |
|
|
50058 |
UINT16 |
Level 2 High SOC alarm |
0.1 % |
|
|
50059 |
UINT16 |
Level 3 High SOC alarm |
0.1 % |
|
|
50060 |
UINT16 |
High SOC alarm return value |
0.1 % |
|
|
50061 |
UINT16 |
Level 1 Pack high differential voltage alarm |
0.1 V |
Cumulative differential voltage |
|
50062 |
UINT16 |
Level 2 Pack high differential voltage alarm |
0.1 V |
Cumulative differential voltage |
|
50063 |
UINT16 |
Level 3 Pack high differential voltage alarm |
0.1 V |
Cumulative differential voltage |
|
50064 |
UINT16 |
Pack high differential voltage alarm return value |
0.1 V |
Cumulative differential voltage |
|
50065 |
UINT16 |
Level 1 High pole temperature alarm |
°C |
|
|
50066 |
UINT16 |
Level 2 High pole temperature alarm |
°C |
|
|
50067 |
UINT16 |
Level 3 High pole temperature alarm |
°C |
|
|
50068 |
UINT16 |
High pole temperature alarm return value |
°C |
|