Appendix 7. Alarm Parameter Information
NOTE |
|---|
The following data can be accessed by the read function code |
REGISTER ADDRESS | DATA TYPE | DATA DESCRIPTION | DATA UNIT | COMMENTS |
|---|---|---|---|---|
50001 | UINT16 | Level 1 single cell max voltage alarm | mv | |
50002 | UINT16 | Level 2 single cell max voltage alarm | mv | |
50003 | UINT16 | Level 3 single cell max voltage alarm | mv | |
50004 | UINT16 | Single cell max voltage alarm return value | mv | |
50005 | UINT16 | Level 1 single cell low voltage alarm | mv | |
50006 | UINT16 | Level 2 single cell low voltage alarm | mv | |
50007 | UINT16 | Level 3 single cell low voltage alarm | mv | |
50008 | UINT16 | Single cell low voltage alarm return value | mv | |
50009 | UINT16 | Level 1 single cell large differential alarm | mv | |
50010 | UINT16 | Level 2 single cell large differential alarm | mv | |
50011 | UINT16 | Level 3 single cell large differential alarm | mv | |
50012 | UINT16 | Single cell large differential voltage alarm return value | mv | |
50013 | UINT16 | Level 1 Total cell high voltage alarm | 0.1 V | |
50014 | UINT16 | Level 2 Total cell high voltage alarm | 0.1 V | |
50015 | UINT16 | Level 3 Total cell high voltage alarm | 0.1 V | |
50016 | UINT16 | Total cell high voltage alarm return value | 0.1 V | |
50017 | UINT16 | Level 1 Total cell low voltage alarm | 0.1 V | |
50018 | UINT16 | Level 2 Total cell low voltage alarm | 0.1 V | |
50019 | UINT16 | Level 3 Total cell low voltage alarm | 0.1 V | |
50020 | UINT16 | Total cell low voltage alarm return value | 0.1 V | |
50021 | UINT16 | Level 1 High discharge current alarm | 0.1 A | |
50022 | UINT16 | Level 2 High discharge current alarm | 0.1 A | |
50023 | UINT16 | Level 3 High discharge current alarm | 0.1 A | |
50024 | UINT16 | High discharge current alarm return value | 0.1 A | |
50025 | UINT16 | Level 1 High charge current alarm | 0.1 A | |
50026 | UINT16 | Level 2 High charge current alarm | 0.1 A | |
50027 | UINT16 | Level 3 High charge current alarm | 0.1 A | |
50028 | UINT16 | High charge current alarm return value | 0.1 A | |
50029 | UINT16 | Level 1 Low insulation alarm | kΩ | |
50030 | UINT16 | Level 2 Low insulation alarm | kΩ | |
50031 | UINT16 | Level 3 Low insulation alarm | kΩ | |
50032 | UINT16 | Low insulation alarm return value | kΩ | |
50033 | UINT16 | Level 1 Charging high temperature alarm | °C, +40 | BMS sends with real data +40°C |
50034 | UINT16 | Level 2 Charging high temperature alarm | °C, +40 | BMS sends with real data +40°C |
50035 | UINT16 | Level 3 Charging high temperature alarm | °C, +40 | BMS sends with real data +40°C |
50036 | UINT16 | Charging high temperature return value | °C | |
50037 | UINT16 | Level 1 Charging low temperature alarm | °C, +40 | BMS sends with real data +40°C |
50038 | UINT16 | Level 2 Charging low temperature alarm | °C, +40 | BMS sends with real data +40°C |
50039 | UINT16 | Level 3 Charging low temperature alarm | °C, +40 | BMS sends with real data +40°C |
50040 | UINT16 | Charging low temperature return value | °C | |
50041 | UINT16 | Level 1 Discharge high temperature alarm | °C, +40 | Real data +40°C when sent by BMS |
50042 | UINT16 | Level 2 Discharge high temperature alarm | °C, +40 | Real data +40°C when sent by BMS |
50043 | UINT16 | Level 3 Discharge high temperature alarm | °C, +40 | Real data +40°C when sent by BMS |
50044 | UINT16 | Discharge high temperature alarm return value | °C | |
50045 | UINT16 | Level 1 Discharge low temperature alarm | °C, +40 | Real data +40°C when sent by BMS |
50046 | UINT16 | Level 2 Discharge low temperature alarm | °C, +40 | Real data +40°C when sent by BMS |
50047 | UINT16 | Level 3 Discharge low temperature alarm | °C, +40 | Real data +40°C when sent by BMS |
50048 | UINT16 | Discharge low temperature alarm return value | °C | |
50049 | UINT16 | Level 1 High temperature difference alarm | °C | |
50050 | UINT16 | Level 2 High temperature difference alarm | °C | |
50051 | UINT16 | Level 3 High temperature difference alarm | °C | |
50052 | UINT16 | High temperature difference alarm return value | °C | |
50053 | UINT16 | Level 1 Low SOC alarm | 0.1 % | |
50054 | UINT16 | Level 2 Low SOC alarm | 0.1 % | |
50055 | UINT16 | Level 3 Low SOC alarm | 0.1 % | |
50056 | UINT16 | Low SOC alarm return value | 0.1 % | |
50057 | UINT16 | Level 1 High SOC alarm | 0.1 % | |
50058 | UINT16 | Level 2 High SOC alarm | 0.1 % | |
50059 | UINT16 | Level 3 High SOC alarm | 0.1 % | |
50060 | UINT16 | High SOC alarm return value | 0.1 % | |
50061 | UINT16 | Level 1 Pack high differential voltage alarm | 0.1 V | Cumulative differential voltage |
50062 | UINT16 | Level 2 Pack high differential voltage alarm | 0.1 V | Cumulative differential voltage |
50063 | UINT16 | Level 3 Pack high differential voltage alarm | 0.1 V | Cumulative differential voltage |
50064 | UINT16 | Pack high differential voltage alarm return value | 0.1 V | Cumulative differential voltage |
50065 | UINT16 | Level 1 High pole temperature alarm | °C | |
50066 | UINT16 | Level 2 High pole temperature alarm | °C | |
50067 | UINT16 | Level 3 High pole temperature alarm | °C | |
50068 | UINT16 | High pole temperature alarm return value | °C |