NOTE |
|---|
|
The following data can only be accessed by the read function code |
|
PROCESSOR REGISTER ADDRESS |
DATA TYPE |
DATA DESCRIPTION |
DATA |
COMMENTS |
|---|---|---|---|---|
|
1101 |
UINT16 |
Operation status of battery cabinet |
Bit 0: Initialization
|
EMS / PCS must be processed: operation is permitted only when one of Bit 1, 2, 3, or 4 is set (1). |
|
1102 |
UINT16 |
Pack operation flag (in-service or out-of-service flag)
|
Each bit represents whether a pack is in operation:
|
|
|
1103 |
UINT16 |
Charge/discharge completion flag |
0 - Fully charged flag
|
1: Valid
|
|
1104 |
UINT16 |
Cabinet DIDO status |
Bit 0: RLY1
|
|
|
1105 |
UINT16 |
Cabinet I Alarm Code H |
Alarm codes detailed in Appendix 15 |
|
|
1106 |
UINT16 |
Cabinet I Alarm Code L |
Alarm codes detailed in Appendix 15 |
The alarm codes are passed to the EMS only for the purpose of displaying alarms. |
|
1107 |
UINT16 |
Cabinet II Alarm Code H |
Alarm codes detailed in Appendix 15 |
|
|
1108 |
UINT16 |
Cabinet II Alarm Code L |
Alarm codes detailed in Appendix 15 |
|
|
1109 |
UINT16 |
Cabinet III Alarm Code H |
Alarm codes detailed in Appendix 15 |
|
|
1110 |
UINT16 |
Cabinet III Alarm Code L |
Alarm codes detailed in Appendix 15 |
|
|
1111 |
UINT16 |
Cabinet Maintenance Alarm Code H |
Alarm codes detailed in Appendix 16 |
|
|
1112 |
UINT16 |
Cabinet Maintenance Alarm Code L |
Alarm codes detailed in Appendix 16 |
|
|
1113 |
UINT16 |
Auxiliary Equipment Alarm Code H |
Alarm codes detailed in Appendix 18 |
|
|
1114 |
UINT16 |
Auxiliary Equipment Alarm Code L |
Alarm codes detailed in Appendix 18 |
|
|
1115 |
UINT16 |
Pack in-service or out-of-service flag
|
Each Bit represents whether it is in operation.
|
Bit:
|
|
1116 |
UINT16 |
Pack in-service
|
Each Bit represents whether it is in operation.
|
|