Appendix 15. Level I, II, and III Alarm Codes
NOTE |
|---|
|
Alarm Category | Alarm name | Alarm code | Bit | Comment |
|---|---|---|---|---|
Class I Alarm Code H (includes Level I, II, and III alarm codes) | High temperature rise | 0x0001 | Bit 0 | 1: Alarm generated |
High single pack voltage | 0x0002 | Bit 1 | ||
Class I Alarm Code L (includes Level I, II, and III alarm codes) | High discharge temperature | 0x0001 | Bit 0 | |
Low discharge temperature | 0x0002 | Bit 1 | ||
High monomer voltage | 0x0004 | Bit 2 | ||
Low monomer voltage | 0x0008 | Bit 3 | ||
High differential voltage of single unit | 0x0010 | Bit 4 | ||
Low SOC | 0x0020 | Bit 5 | ||
High SOC | 0x0040 | Bit 6 | ||
Reservation | 0x0080 | Bit 7 | ||
High charging current | 0x0100 | Bit 8 | ||
High discharging current | 0x0200 | Bit 9 | ||
Large difference in temperature | 0x0400 | Bit 10 | ||
Low insulation | 0x0800 | Bit 11 | ||
High total voltage | 0x1000 | Bit 12 | ||
Low total voltage | 0x2000 | Bit 13 | ||
High charging temperature | 0x4000 | Bit 14 | ||
Low charging temperature | 0x8000 | Bit 15 |