Offset address P = 4500 + 100 * n (n represents the number of packs, 0 ≤ n < 32, n = 0 represents the first pack)
|
NOTE |
|---|
|
The following data can only be accessed by the read function code |
|
PROCESSOR REGISTER ADDRESS |
DATA TYPE |
DATA DESCRIPTION |
DATA |
COMMENTS |
|---|---|---|---|---|
|
P+1 |
UINT16 |
Battery pack n in run status |
Bit 0: Initialization status
|
Battery pack operation status |
|
P+2 |
UINT16 |
Pack Relay Status |
Bit 0: Main positive relay
|
|
|
P+3 |
UINT16 |
Pack n-I alarm code H |
See Appendix 15 for alarm codes |
|
|
P+4 |
UINT16 |
Pack n-I alarm code L |
See Appendix 15 for alarm codes |
|
|
P+5 |
UINT16 |
Pack n-II alarm code H |
See Appendix 15 for alarm codes |
|
|
P+6 |
UINT16 |
Pack n-II alarm code H |
See Appendix 15 for alarm codes |
|
|
P+7 |
UINT16 |
Pack n-III alarm code L |
See Appendix 15 for alarm codes |
|
|
P+8 |
UINT16 |
Pack n-III alarm code H |
See Appendix 15 for alarm codes |
|
|
P+9 |
UINT16 |
Pack n - Maintenance alarm code 1 H |
See Appendix 16 for alarm codes |
|
|
P+10 |
UINT16 |
Pack n - Maintenance alarm code 1 L |
See Appendix 16 for alarm codes |
|
|
P+11 |
UINT16 |
Pack n - Maintenance alarm code 2 H |
See Appendix 17 for alarm codes |
|
|
P+12 |
UINT16 |
Pack n - Maintenance alarm code 2 L |
See Appendix 17 for alarm codes |
|
|
P+13 |
UINT16 |
Pack number |
|
|