Appendix 4. Battery Pack Status
Offset address P = 4500 + 100 * n (n represents the number of packs, 0 ≤ n < 32, n = 0 represents the first pack)
NOTE |
|---|
The following data can only be accessed by the read function code |
PROCESSOR REGISTER ADDRESS | DATA TYPE | DATA DESCRIPTION | DATA | COMMENTS |
|---|---|---|---|---|
P+1 | UINT16 | Battery pack n in run status | Bit 0: Initialization status | Battery pack operation status |
P+2 | UINT16 | Pack Relay Status | Bit 0: Main positive relay | |
P+3 | UINT16 | Pack n-I alarm code H | See Appendix 15 for alarm codes | |
P+4 | UINT16 | Pack n-I alarm code L | See Appendix 15 for alarm codes | |
P+5 | UINT16 | Pack n-II alarm code H | See Appendix 15 for alarm codes | |
P+6 | UINT16 | Pack n-II alarm code H | See Appendix 15 for alarm codes | |
P+7 | UINT16 | Pack n-III alarm code L | See Appendix 15 for alarm codes | |
P+8 | UINT16 | Pack n-III alarm code H | See Appendix 15 for alarm codes | |
P+9 | UINT16 | Pack n - Maintenance alarm code 1 H | See Appendix 16 for alarm codes | |
P+10 | UINT16 | Pack n - Maintenance alarm code 1 L | See Appendix 16 for alarm codes | |
P+11 | UINT16 | Pack n - Maintenance alarm code 2 H | See Appendix 17 for alarm codes | |
P+12 | UINT16 | Pack n - Maintenance alarm code 2 L | See Appendix 17 for alarm codes | |
P+13 | UINT16 | Pack number |