NOTE |
|---|
|
The following data can be accessed by the read function code |
|
Processor Register Address |
Data Type |
Data Content |
Data |
Comment |
|---|---|---|---|---|
|
50301 |
UINT16 |
Starting passive equalization – starting differential Voltage value |
mV |
|
|
50302 |
UINT16 |
Minimum cell voltage value to initiate passive equalization |
mV |
|
|
50303 |
UINT16 |
Fan On Temperature |
°C, +40 |
Real data +40 when sent by BMS |
|
50304 |
UINT16 |
Fan Off Temperature |
°C, +40 |
Real data +40 when sent by BMS |
|
50305 |
UINT16 |
Fan Unit Voltage |
mV |
|
|
50306 |
UINT16 |
Maximum allowable current for single pack charging |
0.1 A |
|
|
50307 |
UINT16 |
Minimum allowable current for single pack charging |
0.1 A |
|
|
50308 |
UINT16 |
Charge current reduction voltage |
mV |
|
|
50309 |
UINT16 |
Charge stop cell voltage value |
mV |
|
|
50310 |
UINT16 |
Maximum allowable current for single pack discharge |
0.1 A |
|
|
50311 |
UINT16 |
Minimum allowable current for single pack discharge |
0.1 A |
|
|
50312 |
UINT16 |
Discharge reduction cell voltage |
mV |
|
|
50313 |
UINT16 |
Discharge stop cell voltage |
mV |
|
|
50314 |
UINT16 |
Pre-charge voltage |
0.1 V |
|
|
50315 |
UINT16 |
Pack accumulation of total voltage differential alarm values |
0.1 V |
|
|
50316 |
UINT16 |
Cooling setting temperature |
°C |
|
|
50317 |
UINT16 |
Cooling start temperature |
°C |
|
|
50318 |
UINT16 |
Cooling stop temperature |
°C |
|
|
50319 |
UINT16 |
Heating setting temperature |
°C |
|
|
50320 |
UINT16 |
Heating start temperature |
°C |
|
|
50321 |
UINT16 |
Heating stop temperature |
°C |
|
|
50322 |
UINT16 |
Self-circulating minimum temperature |
°C |
|
|
50323 |
UINT16 |
Self-circulating maximum temperature |
°C |
|
|
50324 |
UINT16 |
Self-circulating start temperature difference |
°C |
|
|
50325 |
UINT16 |
Self-circulating stop temperature difference |
°C |
|
|
50326 |
UINT16 |
Dehumidifier - Humidity start value |
% |
|
|
50327 |
UINT16 |
Dehumidifier - Humidity stop value |
% |
|
|
50328 |
UINT16 |
Dehumidifier - Heating start value |
°C |
|
|
50329 |
UINT16 |
IP_Addr1_1 |
|
Changes to the IP address are applied after restarting |
|
50330 |
UINT16 |
IP_Addr1_2 |
|
|
|
50331 |
UINT16 |
IP_Addr1_3 |
|
|
|
50332 |
UINT16 |
IP_Addr1_4 |
|
|
|
50333 |
UINT16 |
IP_Addr2_1 |
|
|
|
50334 |
UINT16 |
IP_Addr2_2 |
|
|
|
50335 |
UINT16 |
IP_Addr2_3 |
|
|
|
50336 |
UINT16 |
IP_Addr2_4 |
|
|
|
50337 |
UINT16 |
Enable EMS Communication Fault |
|
|
|
50338 |
UINT16 |
EMS Communication Timeout |
seconds |
60 seconds |